5.9 Troubleshooting without Fault Display ■ Deceleration Takes Too Long With Dynamic Braking Enabled Troubleshooting 5 ■ Motor Hunting Occurs When Operating With a Light Load OYMC TOEP C71060622-01-OY V1000 User Manual 231 Cause Possible Solutions L3-04 is set incorrectly. • Check the Stall Prevention Level during deceleration (L3-04). • If a braking resistor option has been installed, disable Stall Prevention during deceleration (L3-04 = “0”). The deceleration time is set too long. Set deceleration to more appropriate time (C1-02, C1-04, C1-06, C1-08). Insufficient motor torque.
• Assuming parameter settings are normal and that no overvoltage occurs when there is insufficient torque, it is likely that the demand on the motor has exceeded the motor capacity. • Use a larger motor. Reaching the torque limit. • Check the settings for the torque limit (L7-01 through L7-04). • If the torque limit is enabled, deceleration might take longer than expected because the drive cannot output more torque than the limit setting. Ensure the torque limit is set to a large enough value. • Increase the torque limit setting.
• If multi-function analog input terminal A1 or A2 is set to torque limit (H3-02 or H3-10 equals 10, 11, 12, or 15), ensure that the analog input levels are set to the correct levels. • Ensure H3-02 and H3-10 are set to the right levels. • Ensure the analog input is set to the correct value. Load exceeded the internal torque limit determined by the drive rated current. Switch to a larger capacity drive. Cause Possible Solutions Carrier frequency is too high. Lower the carrier frequency setting C6-02. Large V/f setting value at low speeds triggers overexcitation. • Select the proper V/f pattern (E1-03).
• Use parameters E1-04 through E1-10 to set the V/f pattern in relation to the load characteristics. The maximum output frequency and the base frequency reference are not set properly in relationship to each other. Set the proper values for the maximum output frequency and base frequency (E1-04, E1-06). Hunting Prevention is disabled (V/f control only). • Enable Hunting Prevention by setting n1-01 = “1”. • (OLV only) Increase the speed feedback detection control gain and time constant (n2-01, n2-02).