5.9 Troubleshooting without Fault Display ■ Load Falls When Brake is Applied (Hoist-Type Applications) ■ Noise From Drive or Output Lines When the Drive is Powered On ■ Ground Fault Circuit Interrupter (GFCI) Trips During Run ■ Connected Machinery Vibrates When Motor Rotates Excessive Motor Oscillation and Erratic Rotation 232 OYMC TOEP C71060622-01-OY V1000 User Manual Cause Possible Solutions The timing for the brake to close and release is not set properly. • Use frequency reference detection for closing and releasing the brake. • At start: Release the brake after creating enough torque. • At stop: Close the brake when the motor still produces torque.
• Make the following setting changes to hold the brake: • Set the frequency detection inactive during baseblock (L4-07 = 0). • Multi-function contact output terminal will switch on when the output frequency is greater than the frequency detection level set in L4-01. Set L4-01 between 1.0 and 3.0 Hz. • Slipping may occur when stopping because hysteresis is used in Frequency Reference 2 (where the frequency agree setting in L4-02 is 2.0 Hz). To prevent this, change the setting to 0.1 Hz. • Do not use the multi-function contact output setting “During Run” (H2-01 = 0) for the brake signal. Insufficient DC Injection Braking. Increase the amount of DC Injection Braking (b2-02).
Cause Possible Solutions Relay switching in the drive generates excessive noise. • Lower the carrier frequency (C6-02). • Install a noise filter on the input side of drive input power. • Install a noise filter on the output side of the drive. • Place the wiring inside a metal conduit to shield it from switching noise. • Ground the drive and motor properly • Separate the main circuit wiring and the control lines. Cause Possible Solutions Excessive leakage current trips MCCB. • Increase the GFCE sensitivity or use GFCI with a higher threshold. • Lower the carrier frequency (C6-02). • Reduce the length of the cable used between the drive and the motor.
• Install a noise filter or reactor on the output side of the drive. Cause Possible Solutions Poor balance between motor phases. Check drive input power voltage to ensure that it provides stable power.