omron — Motor Does Not Rotate Properly after Pressing RUN Button or After Entering External Run Command

5.9 Troubleshooting without Fault Display Unexpected Noise from Connected Machinery Note: The drive may have trouble assessing the status of the load due to white noise generated when using Swing PWM (C6-02 = 7 to A, or 7 if set for Normal Duty). ■ Oscillation or Hunting Troubleshooting 5 OYMC TOEP C71060622-01-OY V1000 User Manual 233 Cause Possible Solutions The carrier frequency is at the resonant frequency of the connected machinery. Adjust the carrier frequency using parameters C6-02 through C6-05. The drive output frequency is the same as the resonant frequency of the connected machinery.

• Adjust the parameters used for the Jump Frequency function (d3-01 through d3-04) to skip the problem-causing bandwidth. • Place the motor on a rubber pad to reduce vibration. Cause Possible Solutions Insufficient tuning in Open Loop Vector Control. Adjust the following parameters in the order listed. An increase in gain should be followed with an increase in the primary delay time constant. • C4-02 (Torque Compensation Primary Delay Time) n2-01 (Speed Feedback Detection Control [AFR] Time Constant 1) C3-02 (Slip Compensation Primary Delay Time) The response for torque compensation and slip compensation will drop as the time constant is increased.

Auto-Tuning has not yet been performed (required for Open Loop Vector Control). • Perform Auto-Tuning. • Set motor parameters after calculating the proper values. • Change the motor control method to V/f Control (A1-02 = “0”). Insufficient tuning in V/f Control. Adjust the following parameters in the order listed. • .n1-02 (Hunting Prevention Gain Setting) • n1-03 (Hunting Prevention Time Constant Setting) • n1-05 (Hunting Prevention Time Constant in Reverse Direction) when hunting occurs in reverse rotation direction only. Gain is too low when using PID control. Check the period of oscillation and adjust P, I, and D settings accordingly.

The frequency reference is assigned to an external source. • Ensure that noise is not affecting the signal lines. • Separate main circuit wiring and control circuit wiring. • Use twisted-pair cables or shielded wiring for the control circuit. • Increase the analog input time filter constant (H3-13). The cable between the drive and motor is too long. • Perform Auto-Tuning. • Reduce the length of the cable.