B.2 Parameter Table Parameter List B Default setting value is dependent on parameter A1-02, Control Method Selection. The value shown is for A1-02 = 0-V/f Control. Default setting value is 120% when C6-01 is set to 1 (ND) and 150% when C6-01 is set to 0 (HD). Default setting value is dependent on parameter E1-01, Input Voltage Setting. Default setting value is dependent on parameter E5-01, Motor Code Selection. Default setting value is dependent on parameter o2-04, Drive Unit Selection. OYMC TOEP C71060622-01-OY V1000 User Manual 349 No. Name Description Range Def. Control Mode Addr. Hex Pg.
V/f O LV P M L8-15 OL2 Characteristics Selection at Low Speeds Sets the OL2 characteristics at output frequencies below 6 Hz. 0: No OL2 level reduction below 6Hz. 1: OL2 level is reduced linearly below 6 Hz. It is halved at 0 Hz. 0,1 1 A A A 4BB — L8-18 Soft CLA Selection Selects the software current limit function. Typically no adjustment is required. 0: Disabled 1: Enabled 0,1 1 A A − 4BE — L8-19 Frequency Reduction Rate during OH Pre-Alarm Specifies the frequency reference reduction gain at overheat prealarm when L8-03 = 4. 0.1 to 1.0 0.8 A A A 4BF — L8-29 Current Unbalance Detection (LF2) Selects the detection of unbalanced output currents caused by faulty devices in the output circuit.
0: Disabled 1: Enabled 0 to 1 1 − − A 4DF — L8-35 Installation Method Selection Selects the installation type: 0: Standard installation of Open Chassis drive 1: Side-by-Side installation with top cover removed 2: Standard Installation of NEMA Type 1 drive 3: Finless / Fin outside installation 0 to 3 Α Α A 4ECH — L8-38 Carrier Frequency Reduction Provides protection to the IGBTs by reducing the carrier frequency at low speeds. 0: Disabled 1: Enabled below 6Hz 2:
Enabled for the whole speed range 0 to 2 A A A 4EF — L8-40 Carrier Frequency Reduction Time Sets the time for that the drive continues running with reduced carrier frequency after the carrier reduction condition has gone (see also L8-38). A setting of 0.00 s disables the carrier frequency reduction time. 0.00 to 2.00 0.50 A A A 4F1 L8-41 Current Alarm Selection Configures an alarm when the output current exceeds 150% of the drive rated current. 0: Alarm disabled. 1: Alarm enabled (alarm is output). 0,1 0 A A A 4F2 —