B.2 Parameter Table 362 OYMC TOEP C71060622-01-OY V1000 User Manual No. Name Description Analog Output Level Unit Control Mode Addr. Hex V/f O LV P M U1-11 Output Terminal Status Displays the output terminal status. U1-11=000 1: Multi-Function Digital Output (fault) (terminal MA/MB-MC) 1: Multi-Function Digital Output 1 (terminal P1) enabled 1: Multi-Function Digital Output 2 (terminal P2) enabled No output signal available – A A A 4A U1-12 Drive Status Verifies the drive operation status. U1-12=00000000 1: During run 1: During zero-speed 1: During REV 1: During fault reset signal input 1: During speed agree 1: Drive ready 1: During alarm detection 1:

During fault detection No output signal available – A A A 4B U1-13 Terminal A1 Input Level Displays the analog input A1 input level. 100% when the input is 10 V 10 V: 100% 0.1% A A A 4E U1-14 Terminal A2 Input Level Displays the analog input A2 input level. 100% when the input is 10 V / 20 mA 10 V: 100% 0.1% A A A 4F U1-16 Output Frequency after Soft Starter Displays the output frequency including ramp times, S-curves. Units are determined by o1- 03. 10 V: Max frequency 0.01 Hz A A A 53