omron — Default Settings Determined by Drive Capacity (o2-04) and ND/HD Selection (C6-01)

B.2 Parameter Table Parameter List B OYMC TOEP C71060622-01-OY V1000 User Manual 381 No. Description Unit Setting Range − Model VZA† − 47P5 4011 4015 C6-01 Normal/Heavy Duty Sel.

− HD ND HD ND HD ND o2-04 Drive Unit Selection − 9A 9C 9D E2-11 (E4-11, T1-02) Motor rated power kW 7.5 11.0 11.0 15.0 15.0 18.5 b3-06 Speed Search current 1 − 0.5 0.5 0.5 0.5 0.5 0.5 b8-04 Energy saving coefficient − 145.38 140.88 140.88 126.26 126.26 115.74 C6-02 Carrier frequency − 3 7 3 7 3 7 E2-01 (E4-01, T1-04) Motor rated current A 13.3 19.9 19.9 26.5 26.5 32.9 E2-02 (E4-02) Motor rated slip Hz 1.30 1.70 1.70 1.60 1.60 1.67 E2-03 (E4-03) Motor no load current A 4.0 5.6 5.6 7.6 7.6 7.8 E2-05 (E4-05) Motor line-to-line resistance Ω 1.152 0.922 0.922 0.550 0.550 0.403 E2-06 (E4-06) Motor leakage inductance % 15.5 19.6 19.6 17.2 17.2 20.1 E2-10 (E4-10) Motor Iron Loss W 263 385 385 440 440 508 E5-01 Motor Code hex FFFF FFFF FFFF FFFF FFFF FFFF L2-02 Momentary power loss ride-through time s 1 1 2 2 2 2 L2-03 Momentary power loss base block time s 0.8 0.9 0.9 1.0 1.0 1.0 L2-04 Momentary power loss voltage recovery time s 0.3 0.3 0.3 0.6 0.6 0.6 L2-05 UV detection voltage V dc 380 380 380 380 380 380 L3-24 Motor acceleration time s 0.175 0.265 0.265 0.244 0.244 0.317 L8-02 Overheat alarm level °C 110 110 110 110 110 110 L8-09 Ground fault selection − 1 1 1 1 1 1 L8-35 Installation Method Sel.