3.7 Control Circuit Wiring 3.7 Control Circuit Wiring Figure 3.14 * 1 Control circuit V1000 Forward run/stop S1 Electrical Installation Reverse run/stop External fault S3 S2 Option card connector Multi-step speed 1 main/aux switch Fault reset S4 S5 DIP switch S1 V I Digital output 250 Vac, 10 mA to 1 A 30 Vdc, 10 mA to 1 A (default setting) Multi-step speed 2 S6 MA Fault Digital inputs (default setting) +24 V 8 mA 24 V MB Digital output 5 ~ 48 Vdc 2 to 50 mA (default setting) 3 SC DIP switch S3 * 2 Source Sink MC Shield ground terminal 0 V P1 Frequency agree (photocoupler 2) During Run (photocoupler 1) RP Setting power supply +10.5 max. 20 mA Pulse train input (max.
32 kHz) P2 PC Photocoupler output common Main speed frequency reference. Multi-function programmable 2 k Ω +V A1 0 to +10 V (20 k Ω ) MP Pulse train output 0 to 32 kHz Analog monitor output AC A2 0 to +10 V (20 k Ω ) (0)4 to 20 mA (250 Ω ) AM AC AM + - 0 to +10 Vdc (2 mA) Safety switch Termination Monitor output Safe Disable Input H2 H1 Jumper HC MEMOBUS/ Modbus comm. RS-485/422 Figure 3.14 Control Circuit Connection Diagram main circuit terminal shielded line twisted-pair shielded line control terminal * 1. Connected using sequence input signal (S1 to S6) from NPN transistor;Default:sink mode (0 V com) * 2.
Use only the +24 V internal power supply in sinking mode; the source mode requires an external power supply. Refer to I/O Connections on page 73 . NOTICE: Do not solder the ends of wire connections to the drive. Soldered wire connections can loosen over time. Improper wiring practices could result in drive malfunction due to loose terminal connections. OYMC TOEP C71060622-01-OY V1000 User Manual 65 DIP switch S2 resistor 120 Ω, 1/2 W Comm. connector R+ R- S+ S- IG hield ground