3.7 Control Circuit Wiring ◆ Control Circuit Terminal Block Functions Drive parameters determine which functions apply to the multi-function digital inputs (S1 to S6), multi-function digital outputs (MA, MB), multi-function pulse inputs and outputs (RP, MP) and multi-function photocoupler outputs (P1, P2). The default is called out next to each terminal. Refer to Figure 3.14 on page 65 WARNING! Sudden Movement Hazard. Always check the operation and wiring of control circuits after being wired. Operating a drive with untested control circuits could result in death or serious injury. WARNING! Confirm the drive I/O signals and external sequence before starting test run.
Setting parameter A1-06 may change the I/O terminal function automatically from the factory setting. Refer to Application Presets on page 107 . Failure to comply may result in death or serious injury. NOTICE: Do not switch an input contactor more often than once every 30 minutes. Improper equipment sequencing could shorten useful life of the drive electrolytic capacitors and circuit relays. Normally the drive I/O should be used to stop and start the motor. ■ Input Terminals Table 3.6 Control Circuit Input Terminals 66 OYMC TOEP C71060622-01-OY V1000 User Manual Type No.
Terminal Name (Function) Function (Signal Level) Default Setting Multi- Function Digital Inputs S1 Multi-function input 1 (Closed: Forward run, Open: Stop) Photocoupler 24 Vdc, 8 mA Note: Drive preset to sinking mode. When using source mode, set DIP switch S3 to allow for a 24 Vdc (±10%) external power supply. Refer to page 73. S2 Multi-function input 2 (Closed: Reverse run, Open:
Stop) S3 Multi-function input 3 (External fault (N.O.)) S4 Multi-function input 4 (Fault reset) S5 Multi-function input 5 (Multi-step speed reference 1) S6 Multi-function input 6 (Multi-step speed reference 2) SC Multi-function input common (Control common) Sequence common HC Power supply for safe disable inputs +24 Vdc (max 10 mA allowed) Safe Disable Input H1 Safe disable input 1 One or Both Open: Output disabled (always use both inputs) Closed: Normal operation Note: Disconnect wire jumper between HC, H1 and H2 when using safe disable input. The wire length should not exceed 30 m. H2 Safe disable input 2