omron — Control Circuit Terminal Block Functions

3.7 Control Circuit Wiring ■ Output Terminals Table 3.7 Control Circuit Output Terminals Connect a suppression diode as shown in Figure 3.15 when driving a reactive load such as a relay coil. Ensure the diode rating is greater than the circuit voltage. OYMC TOEP C71060622-01-OY V1000 User Manual 67 Type No. Terminal Name (Function) Function (Signal Level) Default Setting Main Frequency Reference Input RP Multi-function pulse train input (frequency reference) Response frequency: 0.5 to 32 kHz (Duty Cycle: 30 to 70%) (High level voltage: 3.5 to 13.2 Vdc) (Low level voltage: 0.0 to 0.8 Vdc) (input impedance:

3 kΩ) +V Analog input power supply +10.5 Vdc (max allowable current 20 mA) A1 Multi-function analog input 1 (frequency reference) Input voltage 0 to +10 Vdc (20 kΩ) resolution 1/1000 A2 Multi-function analog input 2 (frequency reference) Voltage or current input (Selected by DIP switch S1) 0 to +10 Vdc (20 kΩ) resolution: 1/1000 4 to 20 mA (250 Ω) or 0 to 20 mA (250 Ω) resolution: 1/500 AC Frequency reference common 0 Vdc 3 Type No. Terminal Name (Function) Function (Signal Level) Default Setting Multi-Function Digital Output MA N.O. (fault) Digital output 30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A MB N.C.

output (fault) MC Digital output common Multi-Function Photocoupler Output P1 Photocoupler output 1 (During run) Photocoupler output 48 Vdc, 2 to 50 mA P2 Photocoupler output 2 (Frequency agree) PC Photocoupler output common Monitor Output MP Pulse train output (Output frequency) 32 kHz (max) AM Analog monitor output 0 to 10 Vdc (2 mA or less) Resolution: 1/1000 AC Monitor common 0 V