Delta Electronics AH — 2.2.2 Wiring Power Supply Modules

AH Motion Controller – Operation Manual Points for attention: 1. The surge absorber and the PLC system should be grounded separately. 2. Please select the surge absorber whose working voltage is not less than the maximum allowable input voltage.  Ground  The diameter of the ground should not be less than the AHPS05-5A AHPS15-5A Another piece of equipment diameters of the cables connected to the terminals L and N.  If much equipment is used, please use single-point ground. The single-point ground is better. _2  If single-point ground cannot be used, please use AHPS05-5A AHPS15-5A A nother piece of equipment common-point ground. The common-point ground is permitted.

AHPS05-5A AHPS15-5A Another piece of equipment  You cannot ground equipment in the way shown on the right.  Wiring Power Supply Modules The equipment can not be grounded in this way.  Connecting an AC power cable *1. 24V on the external power supply is connected to VS+ and VS- on the power supply module. VS+ and VS- can be used to detect whether the voltage of the external power supply is stable. *2. FG on the power supply module is connected to the control box as the functional ground. *3. The live wire and the neutral wire in the AC power cable are connected to L and N on the power supply module 2-8