User Manual of EM760 High-Performance Inverter 294 F04.00 Start-up method 0: direct start 1: start of speed tracking 0 O 0x0400 F04.01 Start frequency 0.00~50.00 Hz 0.00 O 0x0401 F04.02 Start frequency hold time 0.00-60.00, 0.00 is invalid s 0.00 O 0x0402 F04.03 Starting current of DC braking 0.0 to 100.0 (100.0 = rated current ofmotor) % 50.0 O 0x0403 F04.04 Starting time of DC braking 0.00~30.00, 0.00 invalid s 0.00 O 0x0404 F04.06 Pre-excitation current 10.0~500.0 (100.0 = no-load current) % 100.0 O 0x0406 F04.07 Pre-excitation time 0.00~10.00 s 0.10 O 0x0407 F04.08 Speed tracking mode Ones place: Tracking start frequency 0: maximum frequency 1: stop frequency 2:
power frequency Tens place: Selection of search direction 0: search only in command direction 1: Search in the opposite direction if the speed cannot be found in the command direction 01 O 0x0408 F04.10 Deceleration time of speed tracking 0.1~20.0 s 2.0 O 0x040A F04.11 Speed tracking current 30.0-150.0 (100.0 = rated current of inverter) % 50.0 O 0x040B F04.12 Speed tracking compensation gain 1.00~10.00 1.00 O 0x040C F04.14 Acceleration and deceleration mode 0: linear acceleration and deceleration 1: acceleration and deceleration of continuous S curve 2:
acceleration and deceleration of intermittent S curve 0 O 0x040E F04.15 Starting time of S curve in acceleration 0.00 to system acceleration time/2 (F15.13=0) 0.0 to system acceleration time/2 (F15.13=1) 0 to system acceleration time/2 (F15.13=2) s 1.00 ● 0x040F F04.16 Ending time of S curve in acceleration s 1.00 ● 0x0410