4-4 Communication Function 4 Functions 4-182 Register No. Function name Function code R/W Monitor and setting parameters Resolution 1291h FE start ratio A113 R/W -100 to FE end ratio 1 [%] 1292h FE end ratio A114 R/W FE start ratio to 100 1 [%] 1293h to 12A4h Not used 12A5h Acceleration curve parameter A131 R/W 1: Small curve to 10: Large curve 12A6h Deceleration curve parameter A132 R/W 1: Small curve to 10: Large curve 12A7h to 12AEh Not used 12AFh Operation frequency input A setting A141 R/W 0: Digital Operator (F001) 1: Digital Operator (FREQ adjuster) 2: Input FV 3: Input FI 4: RS485 communication 5: Option 1 6: Option 2 7:
Pulse train frequency 12B0h Operation frequency input B setting A142 R/W 0: Digital Operator (F001) 1: Digital Operator (FREQ adjuster) 2: Input FV 3: Input FI 4: RS485 communication 5: Option 1 6: Option 2 7: Pulse train frequency 12B1h Operator selection A143 R/W 0: Addition (A + B) 1: Subtraction (A - B) 2: Multiplication (A × B) 12B2h Not used 12B3h Frequency addition amount A145 (HIGH) R/W 0 to 40000 0.01 [Hz] 12B4h A145 (LOW) R/W 12B5h Frequency addition direction A146 R/W 0: Frequency reference + A145 1:
Frequency reference - A145 12B6h to 12B8h Not used 12B9h EL-S-curve ratio 1 during acceleration A150 R/W 0 to 50 1 [%] 12BAh EL-S-curve ratio 2 during acceleration A151 R/W 0 to 50 1 [%] 12BBh EL-S-curve ratio 1 during deceleration A152 R/W 0 to 50 1 [%]