技术规格书 高性能、高可靠性电源产品 版本号: V1.0 5U200A 嵌入式电源 Table of contents 1) 2) 3) 第 1 页 共 1 0 页
技术规格书 高性能、高可靠性电源产品 版本号: V1.0 5U200A 嵌入式电源 1 、 Overview The 5U200A embedded power supply is a new generation of highly reliable and high-performance communication power supply system designed by the company based on years of experience in development and online operation. The system configuration supports 1-4 rectifier modules that are hot-swappable. The system monitoring module has the function of battery management and power system monitoring. It can realize environmental monitoring by configuring appropriate sensors, and provide multiple sets of backup monitoring data. It can provide RS485 communication interface, which is convenient for remote monitoring and unattended.
This embedded power supply is mainly used in outdoor cabinets. 2 、 The main specifications of the product 3 、 Reference standards and specifications (1)YD/T 1058-2015 "High frequency switching power supply system for communicatio" (2) YD/T 731-2018 "48V Rectifier for Communication" (3) YD/T 585-2010 "Power Distribution Equipment for Communications" (4) YD/T 1051-2018 "General Technical Requirements for Communication Bureau (Station) Power System" 第 2 页 共 1 0 页 Maximum output power Input voltage range Output voltage Output current Rectifiers 12KW 85-300Vac 53.5V 200A RM4850*4(Fully equipped4PCS) Configuration AC input branch:
100A/2P*1, five-hole maintenance socket*1, single-phase smart meter*1, Class C AC SPD*1 Battery access: 100A/1P*2 DC SPD: Class C DC SPD*1 One-off load: 32A/1P*4 Secondary power-off load: 16A/1P*2 A power-off is controlled by the monitor and realized by a 200A normally closed DC contactor. The second power off is controlled by the monitor and realized by a 100A normally closed DC contactor. Specific configuration: can be customized according to customers Optional accessories: Class C lightning protection
技术规格书 高性能、高可靠性电源产品 版本号: V1.0 5U200A 嵌入式电源 (5) YD/T 5040-2005 "Code for Design of Communication Power Equipment Installation Engineering" (6) YD/T 983-2018 "Electromagnetic Compatibility Limits and Measurement Methods for Communication Power Supply Equipment" (7) YD/T 944-2007 "Technical Requirements and Test Methods for Lightning Protection of Communication Power Supply Equipment" (8) YD 5083-2005 "Code for Testing Seismic Performance of Telecommunications Equipment" (9) YD 5096-2016 "Specifications for Testing the Seismic Performance of Communication Power Equipment" (10) QZTT 1007-2014 "Summary of Standards for New Supporting Facilities of China Tower Co., Ltd." (11) QZTT ****-2015 "Embedded High Frequency Switching Power Supply System Monitoring Specification (Trial) 4 、 Principle introduction The principle of the 5U200A embedded power supply system is as follows:
Note: The lightning protection ground, protection ground, and DC working ground are factory defaulted to combine three grounds into one (users can freely split according to use) 第 3 页 共 1 0 页
技术规格书 高性能、高可靠性电源产品 版本号: V1.0 5U200A 嵌入式电源 The power supply of the system is input by the single-phase AC mains through the AC input terminal to supply power to the rectifier module; the monitoring uses the input AC detection function of the module itself to detect the input voltage.
After the output of the rectifier module is concatenated, the negative pole is divided into three paths, one path is output to the negative input terminal of the DC load circuit breaker through the DC contactor of the primary power off, and the other path is output to the negative pole input terminal of the DC load circuit breaker through the DC contactor of the secondary power off, and then One way is output through the shunt to the negative input terminal of the battery circuit breaker. The DC contactor realizes battery over-discharge protection under the control of the monitor.
After the output of the rectifier module is connected, the positive pole directly goes to the positive input terminal of the DC load. 5 、 Environmental Conditions 第 4 页 共 1 0 页 Environmental parameters Environmental conditions Transport environment conditions Storage conditions Remark Project Parameter Unit Clim atic condi tions Temp eratur e Low temperature ℃ -5 -40 -45 It can start at full load at -40°C, and linearly derate 20% at +55~+65°C High temperature ℃ 40 70 70 Humi dity Low relative humidity % 5 / 5 / 3000~4000 derating output High relative humidity % 95 / 95 Condensation yes/no no / no Altitude m 4000 4000 Mech anica l stress condi tions Vibration Sine vibration: 5~9Hz:
amplitude 3.5mm; 9~200Hz: acceleration 10m/s2; 3 axes, frequency sweep vibration 5 times in each direction Random vibration: 2~10Hz: 30m2/s3; 10~200Hz: 3m2/s3; 200~500Hz: 1m2/s3; 3 axes, 30min each direction / Only for subracks, take out the rectifier module and monitoring module during the test Impact (collision) Acceleration 250m/s2; Pulse width 6ms; 500 collisions in 3 axes and 6 directions Acceleration 400m/s2; Pulse width 6ms; 500 collisions in 3 axes and 6 directions / Fall / Drop height 1m; bottom 1 time /