New Functions of DVP24SV2 (in Comparison with DVP28SV) 1. Analog-to-digital modes are added. Two analog input channels (AD0~AD1): The analog input function of a PLC can be enabled only when the PLC runs. The relation among analog input modes, digital values, and conversion time is described below. Registers related to analog input: Mode Digital value Conversion time Voltage 0 V~10 V (12-bit) 0~4000 D1118 Conversion time is limited by a scan cycle. Current 0 mA~20 mA (11-bit) 0~2000 Device Function number D1062 (Latching device) Number of analog input values (AD0~AD1) by which the sum of analog input values is divided: 1~20 Default value:
K2 D1110 Digital average of analog input channel 0 (AD0) If the value in D1062 is 1, the value in D1110 will be the present value of AD0. D1111 Digital average of analog input channel 1 (AD1) If the value in D1062 is 1, the value in D1111 will be the present value of AD1. D1115 (Latching device) Setting an analog input mode Default value: HFFFF: Bit 0~3: AD0 Bit 4~7 : AD1 Analog input modes: 0x0: Voltage mode (0 V~+10 V) 0x1: Current mode (0 mA~+20 mA) 0xF: Disabled Bit 15~8 Bit 7~4 Bit 3~0 D1115 Reserved AD1 AD0 D1118 Analog-to-digital conversion time Unit: ms Not a latching device Default value: K5 Reserved AD1 AD0
Flags related to analog input: Note: The single analog input terminal GND must be connected to SG (common ground). 2. Description of new special auxiliary relays and special data registers Descriptions of special auxiliary relays: Descriptions of special data registers: Device number Function M1588 The input value of AD0 is greater than the maximum value. (The conversion value gotten is greater than 4047 (voltage)/2023 (current).) M1589 The input value of AD1 is greater than the maximum value. (The conversion value gotten is greater than 4047 (voltage)/2023 (current).) Off STOP RUN Special EH3 Function Attribute Latching Default M SV2 On RUN STOP M1326* Fifth group:
CH4 (Y10/Y11) completes the production of pulse output. 24SV2 Off Off - R/W No Off M1327* Sixth group: CH4 (Y12/Y13)) completes the production of pulse output. 24SV2 Off Off - R/W No Off M1568 Fifth group: Users can set the time it takes for CH4 (Y10/Y11) to decelerate the production of pulse output. It is used with D1196. 24SV2 Off - - R/W No Off M1569 Sixth group: Users can set the time it takes for CH5 (Y12/Y13) to decelerate the production of pulse output. It is used with D1197. 24SV2 Off - - R/W No Off M1588* The input value of AH0 is greater than the maximum value. 24SV2 Off Off - R No Off M1589* The input value of AD1 is greater than the maximum value.
24SV2 Off Off - R No Off Off STOP RUN Special EH3 Function Attribute Latching Default D SV2 On RUN STOP D1022 Fifth group: Frequency with which the first section of the pulse output produced by CH4 (Y10/Y11) starts, and frequency with which the last section of the pulse output produced by CH4 (Y10/Y11) ends. 2S4V2 - - - R/W Yes 200
Off STOP RUN Special EH3 Function Attribute Latching Default D SV2 On RUN STOP D1023* Sixth group: Frequency with which the first section of the pulse output produced by CH5 (Y12/Y13) starts, and frequency with which the last section of the pulse output produced by CH5 (Y12/Y13) ends. 24SV2 - - - R/W Yes 200 D1030* Fifth group: Number of pulses produced by CH4 (Y10/Y11) (Low word) 24SV2 - - - R/W Yes 0 D1031* Fifth group: Number of pulses produced by CH4 (Y10/Y11) (High word) 24SV2 - - - R/W Yes 0 D1032 Sixth group: Number of pulses produced by CH5 (Y12/Y13) (Low word) 24SV2 - - - R/W Yes 0 D1033 Sixth group:
Number of pulses produced by CH5 (Y12/Y13) (High word) 24SV2 - - - R/W Yes 0 D1062* Number of analog input values by which the sum of analog input values received by AD0~AD1 is divided: 1~20 24SV2 - - - R/W Yes 2 D1110* Digital average of analog input channel 0 (AD0) If the value in D1062 is 1, the value in D1110 will be the present value of AD0. 24SV2 0 - - R No 0 D1111* Digital average of analog input channel 0 (AD1) If the value in D1062 is 1, the value in D1111 will be the present value of AD1. 24SV2 0 - - R No 0 D1115* Setting an analog input mode Bit 0~3: AD0 Bit 4~7: AD1 K0: Voltage mode (0 V~10 V) K1: Current mode (0 mA~20 mA) K15:
Disabled 24SV2 - - - R/W Yes H’FFFF D1147 Fifth group: Time it takes for CH4 (Y10/Y11) to accelerate/decelerate the production of pulse output. 24SV2 - - - R/W Yes 100 D1149 Sixth group: Time it takes for CH5 (Y12/Y13) to accelerate/decelerate the production of pulse output. 24SV2 - - - R/W Yes 100
Off STOP RUN Special EH3 Function Attribute Latching Default D SV2 On RUN STOP D1196 Fifth group: When M1568 is ON, users can set the time it takes for CH4 (Y10/Y11) to decelerate the production of pulse output. 24SV2 - - - R/W Yes 200 D1197 Sixth group: When M1569 is ON, users can set the time it takes for CH5 (Y12/Y13) to decelerate the production of pulse output. 24SV2 - - - R/W Yes 200