Chapter 9 Troubleshooting 9_ 9-57 Error Code Description Corrective action 16#6405 The number of data which will be received is not consistent with the actual length of the data. Check the command transmitted from the remote device. 16#6501 The remote device involved in the data exchange does not respond after the timeout period. (SM828~SM955) Check the device whose connection number corresponds to the error flag, and check whether it is connected normally. 16#6502 The remote device involved in the data exchange does not respond correctly. (SM828~SM955) Check the device whose connection number corresponds to the error flag, and check whether it is connected normally.

16#6700 MODBUS TCP data exchange initialization error Check the setting value and download the data again. 16#6701 MODBUS TCP data exchange timeout Confirm if the device to be connected supports MODBUS communication protocol. 16#6702 MODBUS TCP data receiving error Confirm if the device to be connected supports MODBUS communication protocol. 16#7002 This function is not available for CPU modules. Check the CPU firmware version. 16#7203 Invalid access code Check the content of the packet sent by the device to be connected. 16#7401 Function code error Check the content of the packet sent by the device to be connected. 16#7402 The packet exceeds the max. data length.

Check the content of the packet sent by the device to be connected. 16#7407 Non-ASCII characters exist in the command. Check the content of the packet sent by the device to be connected. 16#7408 PLC is in RUN mode Data download for program or CPU parameters is not allowed when PLC is in RUN mode. 16#740A The CPU memory is being written or failed to be written. Flash/SD card is being written. Please try again later. 16#740B The Clear or Reset operation is in progress. The RST/CLR operation is in progress. Please try again later. 16#740C The backplane number in a communication command is incorrect. Please check the PLC firmware and the software version and contact the supplier.