Delta Electronics AH — 2.2.3 Wiring AH Motion Controller CPU Modules

Chapter 2 Hardware Setup 2_ *1. If the frequency of input signals received by an input terminal must be 200 kHz, the input terminal must be connected to a 1 kΩ (2 W) resistor in parallel. 2.2.3.2 Wiring AHxxEMC-5A  External devices for AHxxEMC-5A SD 2-13 Terminal Description Response characteristic Rated input Current Voltage X0.12, X0.13, X0.14, X0.15, X1.0, X1.1, X1.2, X1.3 1. Common input terminals. 2. The functions of the terminals:  High-speed count:  The terminals are for counter 2~counter 5.  X0.12 and X0.13 are for counter 2. X0.14 and X0.15 are for counter 3. X1.0 and X1.1 are for counter 4. X1.2 and X1.3 are for counter 5.  High-speed capture:

The terminals can function as trigger signals for high-speed captures.  Interrupt inputs: X0.12, X0.13, X0.14 and X0.15 can function as interrupt inputs. 100kHz(*1) 5mA 24 V Y0.8, 1. Pulse output terminals (open collector). 2. The function of the terminals:  High-speed comparison: The terminals can function as high-speed comparison outputs. 200 kHz 15 mA 24 V Y0.9, Y0.10, Y0.11 MDR36 connector External terminal module RJ45 (EtherCAT) AHxxEMC RUN ERROR ETH Et he rCAT USB MicroSD N1 S TO PRU N C M ic ro S D CAT ther E net ther E RJ45 (Ethernet)