COOLING SYSTEM, AIR-TO-AIR CHARGE COOLING 8.10.4.5 Auxiliary Coolant Flow Path Circuitry Consider the following when using add on components such as cab heater systems, air compressors, auxiliary oil coolers, retarders, exhaust gas cooler, etc.: Location of coolant supply and return connection points. Restriction to coolant flow. Select engine connection points that will give adequate flow under all operating conditions, but do not adversely affect main engine/radiator flow. Location of auxiliary components. Components should be mounted below the top tank or surge tank coolant level whenever possible. This will allow removal of trapped air and to help complete filling of the cooling system.
Special vents which may be required to ensure excessive air can be purged during system fill, if components are mounted above the coolant level. The engine must be run after the system has been filled to purge any remaining trapped air. Add makeup coolant as required. Specific considerations are as follows: Connect auxiliary oil coolers, retarder heat exchangers, and cab and passenger compartment heaters in series with the main coolant flow on the pressure side of the pump. Coolers located on the inlet side of the water pump require modifications to the engine water bypass circuit to provide coolant flow through the cooler during closed thermostat operation.
Modifications must not hinder air from being purged from the water pump. Engine coolant warm-up problems may occur when coolers are located in the radiator bottom tank. Connect the heater supply at the water pump discharge and the return to the thermostat housing base. See the installation drawings on www.detroitdiesel.com for specific locations. Give special care to excessively cold ambient operating conditions. Enhance driver/passenger comfort through the use of highly efficient, low restriction heater cores. Highly efficient, modern engines reject less heat to the coolant. It may be necessary to increase idle speed to maintain coolant temperatures.
8.10.4.6 Water Cooled Exhaust Systems Heat rejection to the JW system will be considerably higher than with a dry exhaust system. Additional vents are required with water cooled components. Consult an authorized distributor or DDC Application Engineering when water cooled exhaust systems are being considered. 8.10.4.7 Water Pumps A water pump is used to circulate the coolant throughout the cooling system, including customer add-on features such as cab heaters, filters, and auxiliary oil coolers. Pumps are sensitive to inlet restrictions, coolant temperature, coolant type and aerated coolant.
Discharge flow can be seriously reduced and damaging cavitation can occur if the cooling system is not designed properly. 8-24 All information subject to change without notice. DDC-SVC-MAN-0073 Copyright © 2009 DETROIT DIESEL CORPORATION