105 Saving Energy with Frequency Converters 4.2 Motor + Frequency Converter Effi ciency The effi ciency of a system consisting of a motor operated by a FC can be calculated by multiplying the single effi ciencies. η System = η Motor * η Frequency converter Typically FC effi ciency curves at two diff erent loads are shown in Fig. 4.2 Effi ciency example of frequency converters (A = 100% load / B = 25% load). The effi ciency of the FC is high throughout the control range, both at high and at low load levels. Fig.
4.2 Effi ciency example of frequency converters Beside the economical aspect that high effi ciencies of FC’s result in lower energy consumption, the dissipated power that has to be removed from the installation is reduced. This is important if the FC is integrated into a cabinet. If the losses are too high separate cooling devices are required which consume energy as well. Normal and part load effi ciencies of motors are compared to the FC as illustrated in Fig. 4. 3 Effi ciency example of a 2-pole motor ( A = 100% load / B = 25% load). Fig. 4.3 Effi ciency example of a 2-pole motor