106 Saving Energy with Frequency Converters Consequently the motor has a major infl uence on the system effi ciency (Fig. 4.4 Effi ciency example of a frequency converter and motor combination ( A = 100% load / B = 25% load). Fig. 4.4 Effi ciency example of a frequency converter and motor combination Although it’s common practice to qualify the effi ciency of the diff erent components, the accuracy of the value depends strongly on the amount of decimal places used . So often the losses of the diff erent components are provided as well. For example 143W losses is much simpler to handle than 90.467% effi ciency (related to 1.5 kW).

4.3 Classifi cation of Energy Effi cient Components Matching individual components to a particular drive system has several advantages over pre-confi gured systems because this allows the engineer to optimise the system to his requirements Pre-confi gured systems are always optimised for general applications and can never fi t all. If available, an indicator for the effi ciency of components is effi ciency classes. Frequency Converter The standard EN 50598-2 defi nes effi ciency classes for FC’s. As power electronics can have several confi gurations the classes IE0-IE2 are defi ned for Complete Drive Modules (CDM) consisting of rectifi er, intermediate circuit and inverter (see Fig.

4.5 Defi nition of CDM and PDS). CDM with ability to feed back e.g. braking energy to the mains are addressed but not covered because they have typically twice the losses.