108 Saving Energy with Frequency Converters Motors For the power range 0,12-1000 kW, effi ciency classes IE1-IE4 for electric motors are defi ned in the standard IEC/EN 60034-30-1. Although the standard is valid for all motor types some motor constructions (e.g. brake motors) are excluded from the standard. Several countries and regions use the IE class limits to defi ne Minimum Effi ciency Performance Standards (MEPS) to restrict the use of low effi ciency motors. The effi ciency class is related to the nominal operating point of the motor. Effi ciencies at full speed but reduced torque must be stated on the nameplate or in the documentation.
Limits are diff erent for supply frequencies (50/60Hz) and the number of motor poles (2, 4 or 6 poles). Classes for motors operated with FC’s are under discussion and will be defi ned in IEC/ EN 60034-30-2. Frequency Converter + Motor Combination Effi ciency classes for Frequency Converter and Motor combination are defi ned in the standard EN 50598-2 via an IES rating. Similar to the CDM, the classes of the so called Power Drive System (PDS), which is the motor + FC combination (see Fig 4.5 Defi nition of CDM and PDS), are related to a reference system (see Fig. 4.7 Defi nition of CDM and PDS effi ciency classes).
PDS with 20% higher losses than the reference are in class IE0 while systems with 20% lower losses are in class IES2. Losses related to reference Losses related to reference CDM PDS IE0 ISE0 125% 120% 100% Reference 100% IE1 IES1 80% 75% IE2 IES2 0% 0% Fig. 4.7 Defi nition of CDM and PDS effi ciency classes The classifi cation is made for 100% relative speed and 100% relative torque. If the FC is designed for a shorter cable or it’s directly mounted on the motor where shorter