109 Saving Energy with Frequency Converters cable can be used this must be stated in the documentation. In general all kind of optimisations are possible as long they are noted in the documentation. Consequently comparing two PDS ratings is diffi cult because they will most likely have diff erent bases. The IES class for FC and drive combinations illustrates the diffi culty in optimising a system and that all components must be carefully selected, in order to optimise the application.
The diff erence between pre-confi gured and non-optimised free combined systems will most often be minor, but matching diff erent components generally allows fi ner adjustment to the machine, giving the machine builder a competitive advantage. 4.4 Energy Effi cient Motor Start The energy for starting a motor can be split into 3 major parts: • Energy required for operating the load • Energy required for accelerating the load and the motor • Losses in motors and control The simplest way for starting a motor is to connect the motor direct on line (DOL) but this is also an ineffi cient solution. The motor will have high losses when starting due to the huge slip when applying the voltage.
While accelerating the motor, the slip and hence the losses are reduced. 800 % Full load current 600 700 500 4 400 200 300 3 2 100 1 0 0 12.5 25 37.5 50 Hz Full load & speed Fig. 4.8 Typical motors currents curves started by (1): Frequency converter at VT load (2): star-delta starter (3): Softstarter (4): direct on line (DOL)