110 Saving Energy with Frequency Converters Softstarters can be used which adjust the motor voltage like Star/Delta starters, but linearly. The device increases the voltage until a programmed current limit is hit. The limit is application-dependent, typically in the range of 300-500% FLC. While the motor is accelerating the current drops and the device increases the voltage further. This sequence continues until the mains voltage level is applied to the motor. 300% 800% 700% 250% 200% 600% Torque [%] 150% Current [%] 500% 400% 100% 300% 50% 200% 100% 0% 0% 20% 40% 60% Speed [%] 0% 20% 40% 60% Speed [%] 80% 100% 0% 80% 100% Fig.
4.9 Comparison motor start direct on mains with motor started by a softstarter (400% current limit) For minimising the losses Softstarters are typically operated in by-pass after the motor has been started. During the starting phase the losses are approx. 4.5 W per A. The most effi cient way for starting a motor is the use of FC’s. As voltage and frequency are controlled the slip and hence the losses are reduced. Using a by-pass like on Softstarters is possible but seldom used. 300% 800% 700% 250% 200% 600% Torque [%] 150% Current [%] 500% 400% 100% 300% 50% 200% 100% 0% 0% 20% 40% 60% Speed [%] 0% 20% 40% 60% Speed [%] 80% 100% 0% 80% 100% Fig.
4.10 Comparison motor start direct on mains with a motor started by a frequency converter at 160% overload Start at mains Soft starter St art at mai ns Softstart er Start at mains Freq uency Con verter St art at mai ns Freque ncy Conve rter