112 Saving Energy with Frequency Converters Maximum Torque Per Ampere This strategy minimises stator current magnitude for a required torque while considering reluctance torques. Variations in inductances during operation must be considered to obtain best results. Constant Unity Power Factor control The angle between current and voltage vector is kept constant under this strategy so the apparent power rating of the inverter can be reduced. In addition FC’s provide extra functionalities for reducing the magnetic fi eld strength at reduced load. This can be done by special U/f characteristics or by Automatic Energy Optimization (AEO) functions.
Automatic Energy Optimisation Start with high acceleration AEO-adjustment Speed Automatic load adjustment Motor current Motor voltage Fig. 4.12 Automatic Energy Optimisation Automatic adjustments take place after the application reaches a steady state. The applied control strategy reduces the magnetisation level and thus the energy consumption. An optimised balance between energy saving and having enough magnetisation for sudden load peaks must be given to ensure reliable operation. See fi g 4.12 Automatic Energy Optimisation. The average energy saving potential for small to medium-sized drives is 3 to 5 % of the rated motor power during operation at low loads.
As a very important side-eff ect, the motor runs almost noiselessly at low loads – even at low to medium switching frequencies.