113 Saving Energy with Frequency Converters 4.6 Load over Time Every component in a system has some losses, so adding components to a system should be avoided if possible. This applies also to FC’s. Adding a unit to a motor which has to run all day at full load and full speed will only result in additional losses. But as soon as reducing speed and torque make sense to the application, the use of a FC will reduce the energy consumption. The achievable savings depend on the load profi le over time, the torque characteristics and the effi ciency of the motor and drive system at the given part load points. 40 35 Time fraction 30 25 20 15 10 5 0 20% 40% 60% 80% 100% Load Fig.

4.13 Load over Time fraction diagram indicates how long a load is operated at part load Part load is used in two diff erent contexts. When a motor is operated from the mains, the feeding motor frequency is fi xed and the speed only varies with load. When the motor is operated by a FC, part load describes torque at a certain speed where the torque characteristic is given by the application. Actually the majority of applications are operated at part load. This is also true for mains driven motors as they are typically oversized. 4.6.1 Applications with Variable Torque Variable torque applications often involve pumps and fans. However, a distinction has to be made in the case of pumps.

Although the most popular types of centrifugal pump have a quadratic torque characteristic, eccentric, vacuum or positive displacement pumps have a constant torque characteristic. The energy saving potential of pumps and fans is very high as these machines follow the affi nity laws.