115 Saving Energy with Frequency Converters If a fan/pump is speed-controlled, the operating point moves along the system chara- cteristic. This moves the unit out of its best effi ciency point and effi ciency will typically decrease slightly but the energy saving due to the reduced speed is still much higher compared to throttle or other mechanical controls. In real applications, the achieved energy savings will diff er from the theoretical because losses in piping and duct -work result in a basic load and thus additional losses.

In pump applications often a minimum speed (application and pump type/make- related) is required for avoiding sedimentation of solids and ensuring suffi cient lubrication of the pump. If the range between minimum speed and speed for the maximum required power is too big the system can be cascaded. When pumps are cascaded, one speed-controlled pump covers the base load. If consumption increases, the frequency converter will switch in more pumps sequentially. The pumps accordingly operate at maximum effi ciency whenever possible. Pump control ensures that the system is always as energy-effi cient as possible. In some applications more than one pump is speed controlled.

Cascades can be used in a similar way for other applications like fans or compressors. 4.6.2 Applications with Constant Torque Applications with constant torque are applications for which the load is typically not signifi cantly altered by the speed. This includes conveyor belts, hoists and mixers. If, for example, an engine block is positioned on a horizontal conveyor belt, the weight of that engine block will not change, regardless of the conveyor belt speed. The torque required to move this engine block is always the same. Of course, the friction and acceleration torque would change according to the operating conditions, but the torque needed to move the load still remains constant.

100% speed, 100% torque 50% speed, 100% torque Torque [Nm] Operating point Operating point Torque [Nm] Energy required Energy required Speed [min -1 ] Speed [min -1 ] Fig. 4.16 Energy required at diff erent speed and loads