veda — Facts Manual

132 Electromagnetic Compatibility • Generic standards deal with specifi c environments and have been mainly developed to fi ll in the lack of specifi c product standards. For residential, commercial and light industry environments the generic immunity standard is EN61000-6-1 and the generic emission standard is EN61000-6-3. For industrial environments the generic immunity standard is EN61000-6-2 and the generic emission standard is EN61000-6-4 • Product standards apply for a specifi c product family. For frequency converters the standard is EN/IEC61800-3 The product standard for frequency converters sets both immunity and emission limits depending on the environment where the FC is used:

residential environment (more strict emission limits, not so high immunity levels) or industrial environment (less strict emission limits, higher immunity levels). Table 5.1 Overview of diff erent EMC standards EN/IEC 61800-3 Category EN55011 Class Generic Standard C1 Class B Residential area EN61000-6-3 C2 Class A, Group 1 Residential area C3 Class A, Group 2 Industrial area EN61000-6-4 C3 (I > 100A) Class A, Group 2, I > 100A Industrial area C4 No limits. Make an EMC plan Industrial area