133 Protection against Electric Shock and Energy Hazards 6 Protection against Electric Shock and Energy Hazards 6.1 General Electrical products are often operated with voltages and currents that are potentially hazardous to people, animals and systems. These hazards can result from physical contact, overloading, short-circuiting, destruction of components or the infl uence of heat or moisture. The resulting potential hazards must be avoided, or at least reduced to an acceptable minimum, by means of precautionary planning and design combined with fault analysis and estimation of the residual risk.
Considerations to ensure safety of Frequency Converters during installation, normal operating conditions and maintenance needs to be addressed during the design and construction of the FC. Also consideration shall be given to minimise hazards resulting from reasonably foreseeable misuse of the FC which might occur during its lifetime. The protection against electrical shock is basically obtained by two levels of protection. • Basic protection which protects the user against electrical shock under normal operating conditions.
The basic protection is normally obtained by physical enclosure or barriers, or clearance /creepage distances • Fault protection which protects the user against electrical shock under a single fault condition. The fault protection in FC’s is normally obtained by use of plastic enclosures or appropriate protective earth connection Additionally, a protective galvanic isolation is provided between the accessible control components/circuits and power components of FC’s. This is to ensure that no dangerous voltage (e.g. mains voltage, DC-voltage and motor voltage) can appear on the control lines.
This would make contact with the control lines potentially lethal, as well as creating a risk of damage to the equipment. The international/European standard IEC/EN61800-5-1 describes in detail the requirement for protection against electrical shock as well as protection against other hazards applicable to FC’s. The enclosure rating of the FC provides protection against injury or damage from contact. An enclosure rating better than IP 21 prevents personal injury due to contact. Compliance with national accident prevention regulations (such as BGV-A3, which is