134 Protection against Electric Shock and Energy Hazards mandatory for electrical equipment in Germany) is also necessary to ensure protection against contact hazards. Temperature and fi re hazards FC’s can pose a fi re hazard as a result of overheating. For this reason, they should be provided with a built-in temperature sensor that stops the operation of the FC if the cooling arrangement fails. Under certain conditions, a motor connected to a FC can restart unexpectedly. For example, this can occur if timers are enabled in the FC or temperature limits are monitored.

Emergency stops Depending on system-specifi c regulations, it may be necessary to fi t an emergency stop switch near the motor. This switch can be incorporated in the mains supply line or the motor cable without damaging either the FC or the motor. 6.2 Mains Supply Systems There are diff erent ways of connecting the mains supply to earth, each with advantages and disadvantages. There are three main earth arrangements, as defi ned in IEC 60364: TN, TT and IT.

The letters stand for T – Terra (lat.) = connection to earth N – Neutral = direct connection to the neutral I – Isolated = no connection/fl oating TN-S system Distribution inside a building must fulfi ll the requirements of a TN-S system, so no combined PEN conductors may be used. The TN-S system has the best EMC performance because the neutral and PE conductors are separated. Thus a current through the N does not produce any eff ects on the voltage potential of the PE. This is the preferred system for frequency converter applications.

The disadvantage of the TN-S system, which is in general the disadvantage of both TN and TT systems, is that in the case of an earth fault on the line, the protection fuses will stop the operation.