veda — Facts Manual

135 Protection against Electric Shock and Energy Hazards Generator or transformer L1 L2 L3 N PE Earth Consumer Fig. 6.1 TN-S system: Separate neutral and PE conductors. TN-C system In the TN-C system the PE and N conductors are combined in a PEN conductor. The disadvantage is that a current through the N conductor is also a current through the PE, thus a voltage potential between earth and the chassis of the connected equipment occurs. In a 50 Hz/60 Hz world, with linear loads, this system does not pose any special issues. But when electronic loads are present, includingFC’s, the high frequency currents that occur can cause malfunctions.

Although this system is compatible with FC’s it should be avoided because of the associated risks. From an EMC perspective the TN-C system is not optimal. Generator or transformer L1 L2 L3 PEN Earth Consumer Fig. 6.2 TN-C system: In the entire system, the neutral conductor and the PE conductor are combined in the PEN conductor. TN-C-S system The TN-C-S system is a hybrid between TN-C and TN-S. From the transformer to the building distribution point the PE and N are common (PEN) – just like in the TN-C system. In the building the PE and N are separated, like in the TN-S.

As the impedance of the PEN conductor between the transformer and the building distribution point is typically low, it reduces the negative eff ects that occur on the TN-C mains.