136 Protection against Electric Shock and Energy Hazards Generator or transformer L1 L2 L3 N PE Earth Consumer Fig. 6.3 TN-C system: In the entire system, the neutral conductor and the PE conductor are combined in the PEN conductor TT system In the TT system the PE at the consumer is provided by a local earth electrode. The main advantage of the TT system is that the high frequency currents in the PE circuit of the consumer are separated from the low frequency currents in the N conductor. From an EMC perspective this is the ideal system.

However, because of the unknown impedance of the earth connection between the earth of the transformer and the earth of the consumer, it cannot be guaranteed that a line to PE short circuit at the consumer will blow the fuses quickly enough and protect against electrical chock. This disadvantage can be mitigated by using residual current devices (RCD). Generator or transformer L1 L2 L3 N Earth Earth Consumer Fig. 6.4 TT system: Earthed neutral conductor and individual equipment/installation earthing IT system In the IT mains the transformer is unearthed and the three phases are fl oating.

The rationale for such a system is the ability of continuing operation after a line to earth fault occurs. Isolation monitoring devices are used for observing the integrity of the isolation between phases and earth. If the isolation is degraded, corrective maintenance can be carried out.