veda — Facts Manual

137 Protection against Electric Shock and Energy Hazards The disadvantage of this system is its poor EMC performance. Indeed, any earth noise current will cause the entire system to fl oat with the noise, possibly causing malfunction of electronic equipment. When FC’s are used on IT mains special considerations have to be taken, for example by disconnecting all capacitors to earth (such as the common-mode capacitors in the RFI fi lter). Consequently, conducted emissions will be unfi ltered and a lot of high frequency noise can be found on IT mains. Generator or transformer L1 L2 L3 Earth Earth Consumer Fig. 6.5 IT system:

Isolated mains; the neutral conductor may be earthed via an impedance or unearthed 6.3 Additional Protection The degradation of the isolation between live parts and chassis leads to earth leakage currents and can compromise both personal safety (risk of electric shock) and equipment safety (the risk of over-heating components that can eventually lead to a fi re). The use of additional protective devices depends on local, industry-specifi c or statutory regulations. There are two types of protection relays for additional protection. One type uses a fault voltage relay, while the other uses a residual current relay.

Additional protection with a fault voltage relay (FU relay) can be provided in most installations. Protection is achieved by connecting the relay coil between the earthing terminal of the FC and the system earthing point. A fault voltage trips the relay and disconnects the FC from the mains. In practice, FU relays are advantageous in situations where earthing is not allowed. Whether or not they are allowed to be used depends on the regulations of the electricity supply company. This form of protection is very rarely used. Earth Leakage protection with a residual current operated circuit breaker (RCCB) is allowable under certain conditions. Residual current operated circuit breakers contain