138 Protection against Electric Shock and Energy Hazards a sum-current transformer. All of the supply conductors for the FC pass through this transformer. The sum-current transformer senses the sum of the currents through these conductors. The sum is zero if there is no leakage current in the installation. If there is a leakage current, the sum is not zero and a current is induced in the secondary winding of the transformer. This current switches off the relay and disconnects the FC from the mains. Conventional RCCBs use inductive sensing and are therefore only suitable for sensing AC currents.
FC’s with B6 input bridge rectifi ers can cause a pure DC current to fl ow in the supply cable in the event of a fault. It is recommended to check whether DC current can be present at the input to the FC. If it can, a Type B RCD (sensitive to both AC and DC) must be used to obtain reliable protection. This type of RCD has additional integrated circuitry that allows it to detect both AC and DC residual current. Fig. 6.6 Fault voltage relay These devices are commonly known as residual current operated circuit breakers (RCCBs). The higher-level term is ”residual current operated device” (RCD) in accordance with EN 61008-1.
Filters and components for RFI suppression (common-mode capacitors) always cause a certain amount of leakage current. The leakage current produced by a single RFI suppression fi lter is usually just a few milliamperes. However, if several fi lters or large fi lters are used, the resulting leakage current may reach the trip level of the RCD. The interference suppression components used with FC’s generate leakage currents. For this reason, the earth connection must be made as follows: • If the leakage current is greater than 3.5 mA, the cross-section of the PE conductor must be at least 10 mmІ