veda — Facts Manual

140 Protection against Electric Shock and Energy Hazards continuously conduct) and speed (which means how long it takes to blow the fuse at a given overcurrent). The higher the current the shorter time it takes to blow the fuse. This is expressed by time current characteristics, as shown in Fig. 6.9 Time-current characteristics of fuses: Fig. 6.9 Time-current characteristics of fuses There are diff erent standardised time-current characteristics depending on the intended application. For protecting FC’s typically aR fuses for semiconductor protection are used to limit the damage in case of a short-circuit or internal component breakdown.

In some situations gG type general purpose fuses can be used. For the specifi c fuse selection it is important to consult the documentation of the FC and strictly follow those recommendations, since the recommended fuses are tested together with the FC.