94 Frequency Converters and Motors The following measures are typically used: • Extend the deceleration ramp time • Dissipate the energy in the motor. That is, the motor is used as a braking resistor • The FC is fi tted with a “brake chopper” electronic circuit and appropriate braking resistors • Use of a regenerative braking unit to feed energy back to mains • Use of FC’s with an active rectifi er to feed energy back to mains The fi rst two measures require no additional hardware components. All the other measures do require additional components and must be taken into account at the design stage of the machinery.
3.5.1 Extending Deceleration Ramp The deceleration ramp time can be extended by the operator by changing the relevant parameter setting. However the operator must judge the load ratios himself. Example An attempt to brake a 22 kW motor operated by a FC from 50 Hz to 10 Hz within one second will end up with the FC tripping because the motor, acting as a generator, will feed back too much energy. The user can prevent the FC from tripping by changing the ramp-down time (for example, to 10 seconds). Alternatively, the modern FC has control functions such as overvoltage control (OVC) that must be enabled to prevent the FC tripping or to automatically extend the ramps.
The FC itself determines then the appropriate ramp time. This type of ramp extension automatically takes account of varying load inertias. Care must be taken when this kind of function is used on machines with vertical or horizontal movement (such as hoists, lifts, and portal cranes) as extending the ramp time does also mean that the traveling distance will be prolonged. 3.5.2 Motor as a Braking Resistor Manufacturers use various methods for using the motor as a braking resistor. The basic principle is based on re-magnetising the motor. Every manufacturer gives its method a diff erent name, such as AC brake, fl ux brake, or compound braking.
This type of braking is not recommended for highly dynamic applications (such as hoists or lifts) because the more frequent the braking, the hotter the motor becomes and consequently it can fail to perform as expected.