96 Frequency Converters and Motors Fig. 3.12 Regenerative braking unit shows a simplifi ed version of the operating principle. AC line supply AC line supply Motoring Motoring DC link DC link a) b) Fig. 3.12 Regenerative braking unit: motoring phase control on (a), motoring phase off (b) For evaluation when it makes economic sense using these kind of devices please refer to chapter 4 Saving Energy with Frequency Converters. 3.6 Static Brake Operation The FC has several functionalities for locking or coasting the motor shaft, such as:

• Coasting to stop • DC brake • DC hold • Electromechanical brake The last three of these functions can typically only be performed after a stop command has been issued. This is often misunderstood in practice. It is important to note that a reference value of 0 Hz does not function as a stop command. In general, do not use these functions when the direction of rotation is reversed. 3.6.1 Coasting to Stop With the motor coasting, the voltage and frequency are immediately interrupted (0 V/0 Hz) and the motor is “released”. As the motor is no longer energised, it will typically spin down to zero speed.

Depending on the speed and inertia of the load this can take from seconds to hours (for example, for huge separators). Gene rating Gene rating