veda — Facts Manual

97 Frequency Converters and Motors 3.6.2 DC Braking A DC voltage across any two of the three motor phases is used to generate a stationary magnetic fi eld in the stator. This fi eld cannot generate high braking torque at the rated frequency. The braking power remains in the motor and may cause overheating. Three parameters are required for DC braking: • The frequency at which the brake should be activated. A frequency value below 10 Hz is recommended. Use the motor slip frequency as a guide. A frequency of 0 Hz means that the function is disabled • The braking current used for holding the motor shaft.

The recommendation is not to exceed the rated current of the motor in order to prevent possible thermal overload • The duration of DC braking. This setting depends on the application 3.6.3 DC Hold Unlike the DC brake, the DC hold has no time limit. Otherwise the above recommendations for the DC brake apply. This function can also be used when “auxiliary heating” is implemented for a motor placed in a very cold environment. As constant current fl ows through the motor, do not exceed the rated motor current. This minimises the thermal load on the motor. 3.6.4 Electromechanical Brake The electromechanical brake is an aid for bringing the motor shaft to a standstill.

This can be controlled from the FC by means of a relay and there are various possible control options. It is important to establish when the brake can be released, as well as hold the motor shaft. Some of the points to consider are: • Motor pre-magnetisation, meaning a minimum amount of current is needed • The frequency at which activation or deactivation occur • Reaction times (delay times) of the relay coils For critical applications such as hoists or lifts, once the start command has been given the brake may only be released after ensuring optimum pre-magnetisation of the motor; otherwise the load could fall.

A minimum current, usually the magnetising current, should fl ow fi rst to ensure that the motor cannot drop the load.