3 Functions of Devices in DVP-PM automatically be defined, and PG1 signal which stops the positioning immediately is only valid when it is out of the mask area. When PG1 is triggered, the clear signal CLR1 will be triggered automatically after 20μs. In addition, the positioning speed is operated according to V(I), and the pulses are sent out by the pulse generator. ♦ The mask area is defined by current position and the target position as below diagrams. If the current position is smaller than the target position, the positioning will be operated in forward direction. If the current positon is bigger than the target position, the positioning will be operated in backward direction.
In both cases, the mask area will be the range between current position and 0. Forward operation Backward operation Operation direction Target position (D1918) Target position (D1918) Operation direction Current position (D1928) Current position (D1928) Mask area Mask area Current position (D1928=0) Current position (D1928=0) ♦ Operation direction: Direction of relative positioning is determined by the sign bit of the value for P(I) (set in D1838, D1918, D1998). Direction of absolute positioning is determined by current position (CP). Forward running occurs when P(I) is bigger than CP. Reverse running occurs when P(I) is smaller than CP.
♦ The operation speed will be stable after the speed is accelerated from V BIAS to the expected V(I). When PG1 is triggered out of the mask area, the positioning stops immediately. ♦ The registers involved: D1824 (D1904, D1984) (V BIAS ), D1840 (D1920, D2000) (V(I)), D1822 (D1902, D1982) (V MAX ), D1838 (D1918, D1998) (P(I)) and D1836 (D1916, D1996) (T ACC ) Speed Time DOG1 PG1 CLR1 20 s µ 9. b8 of D1846 (D1926, D2006, D2086): enabling single-speed positioning ♦ When b[8] is triggered, i.e. single-speed positioning is enabled, and START = ON, the single-speed positioning will be started. The pulse generator will send out pulses according to the setting of P(I) and V(I).
♦ Operation direction: Direction of relative positioning is determined by the sign bit of the value for P(I) (set in D1838, D1918, D1998, D2078). Direction of absolute positioning is determined by current position (CP). DVP-PM Application Manual 3-70 T ACC V MAX V(I) V BIAS V(I) V BIAS