2 Hardware Specifications and Wiring „ DVP20PM „ DVP10PM Digital output points: „ DVP-20PM DVP-PM Application Manual 2-4 Item 24V DC single-ended common point input Note Low speed High speed (200kHz)#1 Spec Change wiring from S/S to SINK or SOURCE #1: Input point A, B and PG are high-speed inputs; others are low-speed input. For 10PM, X0 ~ X7 and X10+ ~ X13+ can be used as general high-speed input points. #2: Input point X0 ~ X7 can conduct 10 ~ 60ms digital filter adjustment.
Input wiring type Input indicator LED display; light on = ON, light off = OFF Input voltage - OFFON 20us Active level ONOFF 30us Response time / noise 10ms 0.5us immunity#2 Item Double-ended differential 24V DC single-ended input common point input Note Spec High speed (200kHz) Independent wiring Change wiring from S/S to SINK or SOURCE #1: Input points support 10 ~ 60ms digital filter adjustment, and 20~85KHz high-frequency digital filter adjustment.
Input wiring type Input indicator LED display; light on = ON, light off = OFF Input voltage 5~24 VDC 24 VDC Input current 15mA OFFON 20us Active level ONOFF 30us Response time / noise 10ms / 0.5us immunity#1 Item Single-ended common point transistor Single-ended common point#1 output#1 relay output Spec Low speed High speed Maximum frequency 10kHz 200kHz For ON/OFF control of load Output indicator LED display; light on = ON, light off = OFF Minimum load - 2mA/DC power supply Working voltage 5 ~ 30VDC Isolation Photocoupler isolation Electromagnetic isolation Resistive 0.5A/1 point (2A/COM) 2A/1 point (5A/COM) Current spec. Inductive 9W (24V DC) #2 Lamp 2W (24V DC) 20W DC/100W AC Max.
output OFFON 20us 0.2us 10ms