Delta Electronics — 9.2.3.1 Start / Stop Cyclic E-CAM

9 Electrical CAM Control steps: Step 1: Initialization (1) Clear the content in registers D1848, D1849, D1862, D1863, D1868. (2) Set up input pulse type as A/B phase (D1864 = H200) (3) Set up pulse output type of Y axis as A/B phase (H30) (4) Set up D1799 (input terminal polarity setting) = 6. MPGA/MPGB are NO contacts (5) Set up operation speed of Y axis variable speed operation (in this case Y axis outputs signals (6) Set up lower bound of CAM sync output D1839, D1838 = 20000 and upper bound D1843, as input signals of Master). D1842 = 30000. Between Master position 20000~30000 (can be monitored by D1862), CLR0 is ON. However, the CLR LED on the MPU will not respond to it.

To monitor CLR signal, you can connect CLR0- with 0V and CLR0+ with Xn input contact then monitor the ON/OFF status of Xn input. Step 2: Set On M0 to enable cyclic E-CAM. When M0 is rising-edge triggered, Master starts to receive the variable speed pulses from Y axis, and Slave operates according to the above E-CAM Data curve. In addition, CLR0 = ON during Master position 20000~30000. Step 3: Reset M0. When M0 is falling-edge triggered, E-CAM stops. Ladder Diagram: M1002 Set up pulse input type as A/B phase Set up D1799 (input terminal polarity setting)= 6. MPGA0/MPGB0 are NO contacts.

M1002 Set up operation speed of Y axis variable speed operation Lower bound of E-CAM sync output Upper bound of E-CAM sync output When D1846=H2000, Y axis variable speed operation executes. M0 LD= D1846 H2000 When M0 is rising-edge triggered, set D1846=H2000 to enable cyclic E-CAM M0 When M0 is falling-edge triggered, cyclic E-CAM stops. DVP-PM Application Manual 9-12 ZRST D1848 D1849 ZRST D1860 D1863 MOV H200 D1864 MOV H30 D1896 MOV K6 D1799 DMOV K5000 D1920 DMOV K20000 D1838 DMOV K30000 D1842 MOV H10 D1926 MOV H2000 D1846 MOV H0 D1846